LCD Display Modes
280
890053-00-02
9.2 Monitor Mode (MON)
The inverter boots up in the Monitor Mode (MON). The inverters operating conditions can be
monitored at the Monitor Mode display. A maximum of four items can be displayed.
Monitor Mode Setting Details
Code
Description
CNF-20
AnyTime Para
CNF-21
Monitor Line-1
CNF-22
Monitor Line-2
CNF-23
Monitor Line-3
Select items to display in the Monitor Mode display. Monitor mode is the first displayed
mode when the inverter is powered on. A total of four items can be displayed
simultaneously. These include the AnyTime parameter (upper right corner of LCD) and
Monitor Lines -1, -2 and -3. Parameters CNF-20~23 all share the same setting options
as listed in the table below.
Setting
Function
0
Frequency
During stop, displays the set frequency. During operation,
displays the actual output frequency (Hz).
1
Speed
During stop, displays the set speed (rpm). During
operation, displays the actual operating speed (rpm).
2
Output Current
Displays output current.
3
Output Voltage
Displays output voltage.
4
Output Power
Displays output power.
5
WHour
Counter
Displays inverter power consumption.
6
DCLink
Voltage
Displays DC bus voltage within the inverter.
7
DI Status
Displays input terminal status of the terminal block.
Starting from the right, displays P7P1.
8
DO Status
Displays output terminal status of the terminal block.
Starting from the right,
Q1, Relay5 <- Relay1.
9
V1 Monitor[V]
Displays the input voltage value at terminal V1 (V).
10
V1 Monitor[%]
Displays input voltage terminal V1 value as a percentage.
If -10V, 0V, +10V is measured,
-100%, 0%, 100% will be displayed.
13
V2 Monitor[V]
Displays input voltage terminal V2 value (V).
14
V2 Monitor[%]
Displays input voltage terminal V2 value as a percentage.
15
I2 Monitor [mA]
Displays input current terminal I2 value (A).
16
I2 Monitor[%]
Displays input current terminal I2 value as a percentage.
17
PID Output
Displays output of PID controller.
18
PID Ref Value
Displays reference value of PID controller.
19
PID Fdb Value
Displays feedback value of PID controller.
20
Now Date
Displays the set Date (AP3-01).
21
Now Time
Displays the set Time (AP3-02).
22
Now Weekday
Displays the set day (AP3-03).
CNF-24
Mon Mode Init
Selecting 1(Yes) initializes CNF-2023.