5.6.5 Multi-Step Frequencies, Speed-L, Speed-M, Speed-H
Multi-step operations (Fixed Speed Inputs) can be assigned to the Px terminals. Seven steps (1
through 7) can be configured using (3) digital input terminals. Refer to section 5.3.3.4, BAS-50 Multi-
step Frequencies (Fixed Speed Inputs) for more details.
Px terminal setting
options
5.6.6 Multi-Step Accel/Decel Times, XCEL-L, XCEL-M, XCEL-H
Digital input terminals can be configured for different Acc and Dec times. Up to 7 acceleration times
and 7 deceleration times can be set. Refer to section 5.3.3.6
BAS-70 Multi-step Acc/Dec Time Configuration for more details.
Px terminal setting
options
5.6.7 Stopping the Acc/Dec Operation
Configure a digital input terminal to ‘14 (XCEL Stop)’ and when activated, stop acceleration or
deceleration to operate the inverter at a fixed frequency.
Px terminal
configuration
5.6.8 RUN Enable (Safety Stop)
When a digital input is set to ‘15 (Run Enable)’, the inverter will only operate when the input is closed
(Enabled). Refer to section 5.6.2 IN-60 Safe Operation Mode for more details. NOTE: this does not
disable “HAND” button operation.
Px terminal setting
options