Parameter Descriptions
167
890053-00-02
5.6.4.5.2 Jog Operation 2-Fwd/Rev Jog by Multi-function Terminal
A terminal that is set for 32 (FWD JOG)’ or 33 (REV JOG)’ also starts the inverter. The table
below lists parameter settings for a forward (or reverse) jog operation. A separate Run (Fx)
command is not required.
Group
Code
Name
LCD Display
Parameter
setting
Setting Range
Unit
DRV
11
Jog frequency
JOG Frequency
10.00
0.50-Maximum
frequency
Hz
12
Jog operation
acceleration time
JOG Acc Time
20.00
0.00-600.00
sec
13
Operation
deceleration time
JOG Dec Time
30.00
0.00-600.00
sec
IN
65~71
Px terminal
configuration
Px Define
(Px: P1~P7)
32
FWD JOG
0-42
-
33
REV JOG
NOTE: The priorities for speed reference inputs and associated Acc/Dec times via digital inputs
are as follows:
Dwell overrides Jog overrides Up/Down overrides Fixed Speed inputs overrides Frq setting. If a different
operation command is entered during a jog operation (other than dwell), it is ignored, and the
operation maintains the jog frequency.