Parameter Descriptions
166
890053-00-02
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
DRV
11
Jog frequency
JOG
Frequency
10.00
0.50-
Maximum
frequency
Hz
12
Jog operation
acceleration time
JOG Acc Time
20.00
0.00-600.00
sec
13
Jog operation
deceleration time
JOG Dec Time
30.00
0.00-600.00
sec
IN
65~71
Px terminal
configuration
Px Define
(Px: P1–P7)
6
JOG
0-42
-
Forward Jog Description Details
Code
Description
IN-6571 Px Define
Select ‘6 (JOG)’ function from IN-65 ~ 71 for one of the inputs.
[Terminal settings for jog operation]
DRV-11
JOG Frequency
Set the operation frequency.
DRV-12
JOG Acc Time
Set the acceleration speed.
DRV-13
JOG Dec Time
Set the deceleration speed.
If a signal is applied to the jog terminal while running (FX applied), the operating frequency changes to
the jog frequency.