If MOT-07 (motor rated voltage) is set to ‘0’, the inverter corrects the output voltage based on the
input voltage in the stopped condition. If the output frequency is higher than the base frequency
and the input voltage is lower than the MOT-07 setting, the inverter will output a voltage based on
the input voltage. The default settings are 230V, 460V or 575V based on the inverter rating.
0, 170-480 (V),
525-600 (V)
5.2.3 MOT-09 Trim Power %
When viewing “Output Power”, use Trim Power % (MOT-09) to scale the displayed power when
compared to measured power.
If the output power displayed on the keypad is lower than expected, increase the set value at MOT-09
(Trim Power %). If the output power displayed on the keypad is higher than expected, decrease this
set value. The output power display is calculated using voltage and current. Use MOT-09 to correct
the error that may occur when the power factor is low.
5.2.4 MOT-10 Power Source - Voltage and Frequency
Set inverter supply (input) voltage. The Low voltage fault level changes automatically based on the set
voltage in MOT-10.
Select the frequency of input power. When the frequency is set to 50 Hz, the frequencies set for
60 Hz (including the maximum frequency and base frequency) will change to 50 Hz. Likewise,
changing the input frequency setting from 50 Hz to 60 Hz will change all related settings from 50
Hz to 60 Hz.