Enter the measured no-load current at the rated frequency. If no-load
current is difficult to measure, enter a current equivalent to 30–50% of
the rated motor current.
For other DRV-09 control mode settings, refer to section 7 Sensorless Vector Control on page 239.
5.1.6 DRV-11 Jog Frequency
The jog operation allows for temporary control of the inverter. There are two was to apply a jog
and start command using the digital input terminals.
•
Jog-1 using a digital input terminal set to JOG along with a start command (Fx or Rx).
•
Jog-2 using a single digital input set to FWD JOG or REV JOG.
Refer to section 5.6.4.5 JOG operation on page165 for more details on Jog functions using digital
inputs.
5.1.7 DRV-15 Torque Boost
5.1.7.1 Manual Torque Boost
Manual torque boost enables users to adjust output voltage during starting and low speed
operation. This setting improves motor starting properties and increases low speed torque.
Configure manual torque boost for loads that require high starting torque.