EasyManua.ls Logo

BENSHAW RSi H2 Series - Exchange

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Descriptions
170
890053-00-02
5.6.11 Exchange
Power Source Transition can be used to switch the power source to the motor from the inverter
output to the main supply power source (commercial power source), and vice versa.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
IN
6571
Px terminal
configuration
Px Define
(Px: P1–P7)
18
Exchange
0-42
-
OUT
31-35
Multi-function relay
items
Relay1-5
17
Inverter
Line
0-43
-
36
Multi-function
output1 items
Q1 Define
18
Comm
Line
0-43
-
Supply Power Transition Setting Details
Code
Description
IN-6571
Px Define
Set one of the digital input terminals (P1~P7) to ‘18
(Exchange)’. Set the two output relays (Relay1 ~ Relay5) to ‘17
(Inverter)’ and ‘18 (Comm Line)’ respectively. When the digital input
is activated, the output relays will change state. An external method
of switching the inverter output to the commercial line is required.
To reverse the transition, deactivate the digital input terminal.
OUT-31~35
Relay 1~5 Define
OUT-36
Q1 Define
Set Relay1 to 17 (inverter line) and Relay2 to 18 (comm line). Relay
operation sequence is as follows.
Relay2
(Comm
Line)

Table of Contents

Related product manuals