5.6.11 Exchange
Power Source Transition can be used to switch the power source to the motor from the inverter
output to the main supply power source (commercial power source), and vice versa.
Set one of the digital input terminals (P1~P7) to ‘18
(Exchange)’. Set the two output relays (Relay1 ~ Relay5) to ‘17
(Inverter)’ and ‘18 (Comm Line)’ respectively. When the digital input
is activated, the output relays will change state. An external method
of switching the inverter output to the commercial line is required.
To reverse the transition, deactivate the digital input terminal.
Set Relay1 to 17 (inverter line) and Relay2 to 18 (comm line). Relay
operation sequence is as follows.