LCD Display Modes
281
890053-00-02
Inverter power consumption
Values are calculated using voltage and current. Power is calculated every second and the
results are accumulated. Setting CNF-62 (WH Count Reset) value to 1(Yes) will reset
cumulated energy consumption. Power consumption is displayed as shown below:
Less than 1,000 kW: Units are in kW, displayed in 999.9 kW format.
1–99 MW: Units are in MW, displayed in 99.99 MWh format.
100999 MW: Units are in MW, displayed in 999.9 MWh format.
More than 1,000 MW: Units are in MW, displayed in 9,999 MWh format and can be displayed
up to 65,535 MW. (Values exceeding 65,535MW will reset the value to 0, and units will return
to kW. It will be displayed in 999.9 kW format).
9.3 Parameter Mode (PAR)
The PAR Mode includes all the inverter parameter groups. Refer to section 4.2 Parameter Lists on
page 82 for all groups included in the Parameter Mode.
9.4 User & Macro Mode (U&M)
Create a unique list of most often used parameters (USR Group). Register user-selected parameters
from the existing parameter groups.
9.4.1 User Group Setting Details
When completed, use the MODE button to move to the U&M Mode and access the USR Group
parameters.
Code
Description
CNF-42
Multi-Key Sel
At CNF-42, Select 1 (UserGrp SelKey) from the multi-function key
setting options. When parameters are selected and registered in the
USR group, the U&M Mode will appear and display user group (USR
Grp) item on the LCD Keypad.
Follow the procedures below to register parameters to a user group.
No
Procedure
1
Set CNF-42 to 1 (UserGrp SelKey). A icon will be
displayed at the top of the LCD display.
2
In the parameter mode (PAR Mode), move to the parameter
you need to register and press the [MULTI] key. For example,
if the [MULTI] key is pressed in the frequency reference in
DRV 01 (Cmd Frequency), the screen below will be displayed.
󰪻 Group name and parameter number of the parameter
󰪼 Name of the parameter