EasyManua.ls Logo

BENSHAW RSi H2 Series - Derating Based on Carrier Frequency

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
380
890053-00-02
13.6.2 Derating based on Carrier Frequency
The continuous rated current of the inverter is derated when the carrier frequency (CON-04) is
increased. Refer to the following tables for derating percentages based on inverter Voltage and HP
rating.
Current Derate %
Carrier Frequency (kHz.)
Voltage
kW
HP
Default
1~3
4~8
9~15
240
5.5~18.5
7.5~25
3
100
70
60
480
5.5~18.5
7.5~25
3
100
65
55
22~30
30~40
3
100
65
50
Current Derate %
Carrier Frequency (kHz.)
Voltage
kW
HP
Default
1~1.5
2
3
4
5
6~7
8~10
240
22~30
30~40
3
100
100
100
94
88
77
60
37~45
50~60
3
100
100
100
88
77
55
-
55~90
75~125
2
100
100
92
84
76
-
-
480
37~55
50~75
3
100
100
100
60
60
60
60
75~90
100~125
3
100
100
100
55
55
55
-
110~315
150~500
2
100
100
76
76
76
-
-
400
650
1.5
100
95
75
75
-
500
800
1.5
100
92
65
65
Current Derate %
Carrier Frequency (kHz.)
Voltage
kW
HP
Default
2.3kHz
3kHz
5kHz
7kHz
10kHz
15kHz
575
5.5~22
7.5~30
2.3
100
100
87
74
55
30
30
40
2.3
100
100
87
74
55
-
37~55
50~75
2.3
100
100
88
77
60
-
75
100
2.3
100
94
77
60
-
-
90
125
2.3
100
92
71
50
-
-

Table of Contents