LCD Display Modes
295
890053-00-02
9.6.7 CNF-44 Delete Trip History
The fault history can be deleted by programming CNF-44 to ‘1, Yes’. Refer to 9.5 Trip Mode (TRP) on
page 288 for more details.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
CNF
44
Trip History deletion
Erase All Tript
0
No
0-1
-
1
Yes
9.6.8 CNF-46 Read, Write, and Save Parameters
Use read, write and save function parameters of the inverter to copy parameters from the inverter
to the LCD keypad or from the LCD keypad to the inverter.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
CNF
46
Parameter read
Parameter
Read
1
Yes
-
-
47
Parameter write
Parameter
Write
1
Yes
-
-
48
Parameter save
Parameter
Save
1
Yes
-
-
Read, Write, and Save Parameter Setting Details
Code
Description
CNF-46
Parameter Read
Copies saved parameters from the inverter to the LCD keypad. Saved
parameters already on the LCD keypad will be deleted and replaced
with copied parameters.
CNF-47
Parameter Write
Copies saved parameters from the LCD keypad to the inverter. Saved
parameters on the inverter will be deleted and replaced with copied
parameters. If an error occurs during parameter writing, previous
saved data will be used. If there is no saved data on the LCD Keypad,
EEP Rom Empty message will be displayed.
CNF-48
Parameter Save
Parameters changes are saved to RAM. The changed values will be
lost if the power is cycled. Select 1 (Yes) at CNF-48 to save the
changed parameters to inverter memory.