PID Control
220
890053-00-02
6 PID Control Group (PID)
PID control is one of the most common auto-control methods. It uses a combination of
proportional, integral, and differential (PID) controls that provide more effective control for
automated systems. The functions of PID control that can be applied to the inverter operation are
as follows:
Purpose
Function
Speed Control
Control speed by using feedback of the existing speed
comparing it to a target speed. The inverter adjusts the output to
maintain a constant speed (the target speed).
Pressure Control
Control pressure by using feedback of the existing pressure
comparing it to a target pressure. The inverter adjusts the output
to maintain a constant pressure.
Flow Control
Control flow by using feedback of the existing flow comparing it
to a target flow. The inverter adjusts the output to maintain a
constant flow.
Temperature Control
Control temperature by using feedback of the existing
temperature comparing it to a target temperature. The inverter
adjusts the output to maintain a constant temperature.
6.1 PID Parameter List
Code
Name
LCD
Display
Setting Range
Initial Value
Property*
Ref.
00
Jump Code
Jump Code
199
50
O
p.74
01
PID mode selection
PID Sel
0
No
0
No
Δ
p.224
1
Yes
03
PID output monitor
PID Output
-
-
X
p.224
04
PID reference monitor
PID Ref Value
-
-
X
p.224
05
PID feedback monitor
PID Fdb Value
-
-
X
p.224
06
PID error monitor value
PID Err Value
-
-
X
p.224
10
PID reference 1 source
selection
PID Ref 1 Src
0
KeyPad
0
Keypad
Δ
p.224
1
V1
3
V2
4
I2
5
Int485
6
Fieldbus
8
Pulse
10
1
V3
11
I3
11
PID reference 1 keypad
value
PID Ref 1 Set
Unit MinUnit Max
Unit Default
O
p.224
12
PID reference 1 auxiliary
source selection
PID
Ref1AuxSrc
0
None
0
None
Δ
p.224
1
V1
3
V2
4
I2
6
Pulse
7
Int 485
8
FieldBus
10
1
V3
11
I3
13
PID reference 1 auxiliary
mode selection
PID
Ref1AuxMod
0
M + (G*A)
0
M+(G*A)
O
p.224
1
M * (G*A)
2
M / (G*A)
3
M + (M * (G*A))
4
M + G * 2 * (A- 50)