Choose one of the digital input terminals and set it to 29 (Timer In).
Activate the terminal to start the timer function.
OUT-31 ~ 35
Relay1~Relay5,
OUT-36 Q1 Define
Set multi-function output terminals to be used as the timer output to 22
(Timer out).
OUT-55
TimerOn Delay,
OUT-56
TimerOff Delay
Set the On Delay time. When the digital input is activated, the output
relay will change state after the On Delay time has passed.
Set the Off Delay time. When the digital input is deactivated, the output
relay will change state after the Off Delay time has passed.
5.6.20 Dis Aux Ref
When using an Auxiliary Reference along with a Main Frequency Reference, a digital input can be set
to ‘29 (dis Aux Ref)’. When activated, the inverter ignores the Auxiliary Reference. Refer to section
5.3.2 BAS-03 Operating with Auxiliary References for more details.
Px terminal setting
options
5.6.21 FWD JOG / REV JOG
A digital input that is set to ’32 (FWD JOG)’ and/or ’33 (REV JOG)’ also starts the inverter. Refer to section
5.6.4.5.2 Jog Operation 2-Fwd/Rev Jog by Multi-function Terminal for more details.
Px terminal setting
options
5.6.22 Fire Mode
A digital input that is set to ’34 (Fire Mode)’ to operate the inverter under emergency situations. See section
5.8.10 PRT-44 Fire Mode on page 205 for more details.
Px terminal setting
options