10.3.4 Parameter Group for Data Transmission
By defining a parameter group for data transmission, the communication addresses registered in
the communication function group (COM) can be used in communication. Parameter group for
data transmission may be defined to transmit multiple parameters at once, into the communication
frame.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
COM
3138
Output
communication
address x
Para Status-x
(x: 18)
-
0000FFFF
Hex
5158
Input
communication
address x
Para Control-x
(x: 18)
-
0000FFFF
Hex
Currently Registered CM Group Parameter
Address
Parameter
Assigned content by bit
0h01000h0107
Status Parameter-1
Status Parameter-8
Parameter communication code value registered at
COM-3138 (Read-only)
0h01100h0117
Control Parameter-1
Control Parameter-8
Parameter communication code value registered at
COM-5158 (Read/Write access)
10.3.5 Parameter Group for User/Macro Group
By defining user/macro parameter groups, communication can be carried out using the user defined
group (USR Grp) and macro group (MCx Grp) addresses that are registered at the U&M mode.
Parameter groups can only be defined when using the keypad.
Currently Registered User Group Parameters
Address
Parameter
Assigned Content by Bit
0h0200
User Grp. Code 1
Parameter value registered at U&M > USR
1 (Read/Write)
0h0201
User Grp. Code 2
Parameter value registered at U&M > USR
2 (Read/Write)
.
.
.
.
.
.
0h023E
User Grp. Code 63
Parameter value registered at U&M > USR
63 (Read/Write)
0h023F
User Grp. Code 64
Parameter value registered at U&M > USR
64 (Read/Write)
Note
When registering control parameters, register the operation speed (0h0005, 0h0380, 0h0381)
and operation command (0h0006, 0h0382) parameters at the end of a parameter control
frame. For example, when the parameter control frame has 5 parameter control items (Para
Control - x), register the operation speed at Para Control-4 and the operation command to
Para Control-5.