5.8.12 PRT-60 Pipe Break Detection
This function detects Pipe Breaks during PID operation. The fault or a warning signal will occur if
the feedback does not reach the level set by users during the operation with the maximum output
(PID maximum output or the maximum speed set).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
PRT
60
Pipe Break Detection
setting
PipeBroken Sel
0
0
None
1
Warning
2
Free-Run
3
Dec
61
Pipe Break Detection
variation
PipeBroken
Dev
97.5
0100
%
62
Pipe Break Detection
time
PipeBroken DT
10.0
06000.0
Sec
OUT
31~36
Relay output 15
Relay1–5
28
Pipe Broken
-
Pipe Break Detection Details
Code
Description
PRT-60
PipeBroken Sel
Select the operation when detecting Pipe Breaks.
Setting
Function
0
None
No operation
1
Warning
The inverter displays a warning message.
2
Free-Run
The inverter free-runs, then stops.
3
Dec
The inverter decelerates, then stops.
PRT-61
PipeBroken Dev
Sets the Pipe Break Detection level. Set the detect level by multiplying the set
value for PRT-61 by PID Reference.
PRT-62
PipeBroken DT
Sets the detect delay time. Pipe Break operates if the Pipe Break situation is
maintained for a set amount of time.
OUT-31~36
Define
An output relay or Q1 can be set to ’28 (Pipe Broken). When a Pipe Break
occurs, the Relay is activated.
In the graph above, Pipe Break detection occurs if the feedback is smaller than the value
calculated by multiplying the two values set at PID-04 and PRT-61 (PID-04 x PRT-61) at the
inverter’s maximum output (when PID output is the maximum set value, or the inverter is running
at the frequency set at MOT-02).