EasyManua.ls Logo

BENSHAW RSi H2 Series - Relay Output On;Off Control

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Descriptions
190
890053-00-02
5.7.6 OUT-67 Relay Output On/Off Control
This feature operates a digital output (Relay1~Relay5 or Q1) based on the analog input level. Set
the On level (OUT-68) to activate the output and the Off level (OUT-69) to deactivate the output.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
OUT
67
Output terminal on/off
control mode
On/Off Ctrl
Src
1
V1
-
-
68
Output terminal on
level
On-C Level
90.00
Output terminal off
level 100.00%
%
69
Output terminal off
level
Off-C Level
10.00
0.00Output
terminal on level
%
OUT
31~35
Multi-function
Relay1~Relay5
Relay 1~5
26
On/Off
-
-
36
Multi-function output
Q1 item
Q1 Define
Multi-function Output On/Off Control Setting Details
Code
Description
OUT-67
On/Off Ctrl Src
Select an analog input to be used for On/Off control.
OUT-68
On-C Level,
OUT-69
Off-C Level
Set the On/Off levels for the output (Relay1~5 or Q1).

Table of Contents