10.2.2 Setting Communication Parameters
Before proceeding with setting communication configurations, make sure that the communication
lines are connected properly. Turn on the inverter and set the communication parameters.
Built-in communication
inverter ID
Built-in communication
protocol
Built-in communication
speed
Built-in communication
frame setting
Transmission delay after
reception
7
*If COM-02 is set to ‘0’ (Modbus RTU), MaxComID is ‘250’. If set to ‘4’ (BACnet), MaxComID is ‘127’.
10.2.2.1.1 Communication Parameters Setting Details
Sets the inverter station ID between 1 and MaxComID.
Select one of the three built-in protocols: Modbus-RTU, BACnet or
Metasys-N2.
Modbus-RTU compatible protocol
Set a communication setting speed up to 115,200 bps.
The maximum setting range changes depending on the protocol.
BACnet: If the COM-02 Int485 Proto setting is BACnet, the available
communication speed settings are 9600 bps, 19200 bps, 76.8 kbps.