5.8.15 PRT-79 Fan Fault Detection
Cooling fan fault
selection
*
150 HP and larger have internal cooling fans. These fans are also included in the Fan Fault
Detection. A warning “InFan Warning” will appear.
Fan Fault Detection Setting Details
Set the cooling fan fault mode.
The inverter output is blocked, and the fan trip is
displayed when a cooling fan error is detected.
When OUT-31–35 (Relay1–5) or OUT-36 (Q1 Define)
are set to ‘8 (FAN Warning)’, the fan error signal is
output, and the operation continues.
OUT-31–35
Relay1–5
OUT-36
Q1 Define
When the parameter value is set to ‘8 (FAN Warning)’, the fan error signal
is output, and operation continues. However, when the inverter inside
temperature rises above a certain level, output is blocked due to
activation of overheat protection.
5.8.16 PRT-80 Option Card Trip
The inverter monitors communication between installed option cards and will fault when a
communication error occurs between the option card and the inverter. The inverter responds to an
Option Trip based on the setting of PRT-80 (motion at option trip).
Operation mode for
option card trip
Operation Mode on Option Trip Setting Details
The inverter output is blocked, and fault information is
shown on the keypad.
The inverter decelerates the motor based on the value set
at PRT-07 (Trip Dec Time).