6.3.3 Pre-PID and Soft Fill Operation
Pre-PID and Soft Fill are two separate operations. Both are used to prevent excessive pressure
from building in the pipe system during the initial stages of pump operation.
Pre-PID - At start, Pre-PID (without PID control) begins and continues at the Pre-PID frequency
(AP1-21) for the time set at AP1-22. The Pre-PID operation continues until either the feedback
value reaches the Soft Fill Set (escape value, AP1-23) or the time (AP1-22) expires. If the system
has built up enough pressure (or other units) to meet the AP1-23 escape value, Normal PI Control
will begin. If the system has not built-up pressure (or other units) to meet the AP1-23 escape
value, Soft Fill operation begins.
Soft Fill operation automatically changes the PI Reference (setpoint) set in PID-10 and PID-11 to
a "Soft Fill" PI Reference (setpoint). The Soft Fill PI Reference performs a series of steps that
increase over time to slowly fill a piping system. The steps are defined by parameters AP1-24 (Fill
Step Set) and AP1-25 Fill Step Time) as defined below. When the system has built up enough
pressure (or other units) to meet the AP1-23 escape value, Normal PI Control will start.
Set to ‘Yes’ to enable both Pre-PID and Soft Fill operation.
Set to ‘No’ to disable Pre-PID and Soft Fill operation.
Set the inverter output frequency during Pre-PID. The Pre-PID operation
continues until either the feedback value reaches the Soft Fill Set (escape
value, AP1-23) or the time (AP1-22) expires.
Set the Pre-PID time. The Pre-PID operation continues for this time period
until either the feedback value reaches the Soft Fill Set (escape value, AP1-
23) or this time expires.
Set the feedback amount. When feedback reaches this amount at any time
during Pre-PID or Soft Fill, the inverter exits the operation and normal PI
Control begins.