10.4.4 Protocol Implementation
The following table summarizes the information required to implement a BACnet system. Refer to
each section of the table to implement a BACnet system properly.
Category
Items
Remarks
BACnet Services
I-Am (Answer to Who-Is, when
broadcast or reset after power-up)
I-Have (Answer to Who-Has)
Read Property
Write Property
Device Communication Control
Ignores Password in Device
Communication Control
Reinitialize Device
Warm/Cold Starts (Supports Password)
Start Backup, End Backup, Start
Restore, End Restore, or Abort Restore
services are NOT available.
Data Link Layer
BACnet communication card
supports an MS/TP Master Data
Link Layer
Supported Standards: MS/TP Available
speed: 9600, 19200, 38400,
and 76800 bps
MAC ID/Device
Object Instance
configuration
Set at COM-01 Int485 ST ID (MAC
ID).
The Device Object Instances are
set at COM-21 and COM-22.
MAX Master
Property
Set at COM-20 (MAX Master Value).
10.4.5 Object Map
Property
Object Type
Device
BI
BV
AI
AO
MSI
MVI
Object Identifier
O
O
O
O
O
O
O
Object Name
O
O
O
O
O
O
O
Object Type
O
O
O
O
O
O
O
System Status
O
Vendor Name
O
Vendor Identifier
O
Model Name
O