EasyManua.ls Logo

BENSHAW RSi H2 Series - Motor Group (MOT)

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Lists
84
890053-00-02
4.2.2 Motor Group (MOT)
Code
Name
LCD Display
Setting Range
Initial value
Property*
Ref.
00
Jump Code
Jump Code
199
10
O
p.74
01
Motor capacity
Motor Capacity
0
0.3HP (0.2 kW)
Dependent on motor
setting
Δ
p.122
1
0.5HP (0.4 kW)
2
1.0HP (0.75 kW)
3
1.5HP (1.1 kW)
4
2.0HP (1.5 kW)
5
3.0HP (2.2 kW)
6
4.0HP (3.0 kW)
7
5.0HP (3.7 kW)
8
5.5HP (4.0 kW)
9
7.5HP (5.5 kW)
10
10.0HP (7.5 kW)
11
15.0HP (11.0 kW)
12
20.0HP (15.0 kW)
13
25.0HP (18.5 kW)
14
30.0HP22.0 kW ()
15
40.0HP (30.0 kW)
16
50.0HP (37.0 kW)
17
60.0HP (45.0 kW)
18
75.0HP (55.0 kW)
19
100.0HP (75.0kW)
20
125.0HP (90.0kW) [1]
21
150.0HP (110.0kW)
22
200.0HP (132.0kW)
23
250.0HP (160.0kW)
24
300.0HP (185.0kW)
26
400.0HP (250.0kW)
27
500.0HP (315.0kW)
29
650.0HP (400.0kW)
30
800.0HP (500.0kW)
02
Base frequency
Base Freq
30.00400.00 (Hz)
60.00
Δ
p.122
40.00-120.00(Hz) IM S/L
30.00180.00 (Hz) PM S/L
2
03
Number of motor poles
Pole Number
2-48
Dependent on motor
capacity setting, MOT-01
Δ
p.122
04
Rated slip speed
Rated Slip
0-3000 (RPM)
Δ
05
Motor rated current
Rated Curr
0.0-1000.0 (A)
Δ
06
Motor no- load current
Noload Curr
0.0-1000.0 (A)
Δ
07
Motor rated voltage
Motor Volt
0, 170-480 (V), 525-600 (V)
230V/460V/575V
Δ
08
Motor efficiency
Efficiency
70-100 (%)
Dependent on MOT-01
Δ
09
Trim power display
Trim Power %
70-130 (%)
100
O
p.122
10
Input power voltage
AC Input Volt
170~264V (7.5HP~125HP)
240 V
O
p.123
320~528V (7.5HP~125HP)
480 V
320~550V (150HP~800HP)
446-660V (7.5HP~125HP)
600 V
11
Auto Tuning
Auto Tuning
0
None
0
None
Δ
p.124
1
All (Rotation type)
2
All (Stdstl) Static type
3
Rs+ Lsigma (Rotation
type)
4
Tr (Stdstl) Static type
2
5
DeadT-volt
6
All (PM)
2
12
Stator resistance
Rs
0.000-9.999 (Ω)
Dependent on motor
setting MOT-01
I
p.124
13
Leakage inductance
Lsigma
0.00-99.99 (mH)
I
14
3
Stator inductance
Ls
0.00-999.9 (mH)
I
15
Rotor Time Constant
Tr
25-5000 (ms)
I
16
4
PM Stator resistance
Rs (PM)
0.000-9.999 (Ω)
Dependent on motor
setting
P
p.124
17
D-axis inductance
Ld (PM)
0.000~1000.0 (mH)
0
P
18
Q-axis inductance
Lq (PM)
0.000~1000.0 (mH)
0
P
19
Flux reference
PM Flux Ref
0.000~1.000 (Wb)
0.147
P
20
Q-axis inductance scale
Lq(PM) Scale
50~150%
100
P
21
PM auto tuning level
Ld,Lq Tune Lev
20.0~50.0%
33.3
P
22
PM auto tuning frequency
Ld,Lq Tune Hz
80.0~150.0%
150.0/100.0
P
[1] Maximum setting of (20) 125 HP when DRV-09 is set to (4) PM Sensorless
[2] IM Sensorless: Does not apply to 230V, 30~125 HP inverters.
PM Sensorless: Does not apply to 230V, 30~125 HP, 460V, 150~800 HP and all 575V Inverters.
[3] MOT-14 and MOT-15 displayed when DRV-09 is set to '3' IM Sensorless.
[4] MOT-16 ~ MOT-22 displayed when DRV-09 is set to '4' PM Sensorless.

Table of Contents