If Acc/Dec times are set to 5 seconds, and multiple frequency references
are used in the operation in 2 steps, at 10 Hz and 30 Hz, each acceleration
stage will take 5 seconds (refer to the graph below).
5.1.3 DRV-06 Command Source Configuration (Start/Stop)
The H2 Series inverter provides several methods to Start and Stop the inverter. Choices include the
keypad, digital input terminals, RS-485 (Modbus), Fieldbus option cards and an Event Timer feature.
Refer to 8.2 Application Group 3 (AP3) on page 269 details on the Event Timer.
5.1.3.1 The Keypad as a Command Source
Set DRV-06 to ‘0 (Keypad)’ to select the keypad as the command source and set the operation direction
at DRV-02 (Keypad Run Dir). Press the [AUTO] button to enter AUTO mode. The display goes to Monitor
mode. The Auto LED flashes to show in Auto mode.
Since the keypad is now the command source, operation starts when the AUTO button is pressed
again. The reference frequency (speed) is based on DRV-07 setting. If DRV-07 is set to ‘0 Keypad’,
the frequency can be set at the Monitor mode, Line-1. Pressing the AUTO button again stops the
inverter.
The OFF button may be used to stop the operation as well, but the inverter operation mode will be
changed to OFF mode.