8.1.4 AP2-38 Decelerating Valve Ramping
This function is used to prevent pump damage due to abrupt deceleration. When the pump
operation frequency reaches the valve ramp frequency (AP2-38 Dec Valve Freq) while decelerating
rapidly based on the deceleration ramp time (set at AP2-42), it begins to slow down the
deceleration based on the deceleration valve ramp time (set at AP2-39 DecValve Time).
Decelerating valve ramp operates when ADV-24 (Freq Limit) is set to ‘1 (Yes)’.
Dec valve ramping
start frequency
Deceleration Valve Ramping Setting Details
Sets the start frequency where the slow deceleration begins in order to prevent
pump damage when the inverter stops. Decelerating valve ramping is
performed from the frequency set at AP2-38 to the frequency limit set at ADV-25
(low frequency limit for pump operation).
Sets the time it takes to decelerate from the frequency set at AP2-38 to the
frequency limit set at ADV-25 (low frequency limit for pump operation).
The time set at AP2-39 refers to the absolute time that it takes for the pump to decelerate from the frequency
set at AP2-38 to the frequency limit set at ADV-25.