5.5.2 CON-13 Anti-hunting Regulation (Resonance Prevention)
This function is used to prevent the hunting of a V/F controlled fan or motor caused by current
distortion or oscillations due to mechanical resonance or other reasons.
Enable or disable
anti- hunting
regulation
(resonance
prevention)
Anti-hunting
regulation P- Gain
Anti-hunting
regulation start
frequency
Anti-hunting
regulation end
frequency
Anti-hunting
regulation
compensation
voltage limit
Anti-hunting Regulation Setting Details
Selects the Anti-hunting regulator operation.
Disable anti-hunting regulation.
Enable anti-hunting regulation.
Increasing AHR proportional gain improves responsiveness of the
anti-hunting regulation. However, current oscillation may result if AHR
proportional gain is set too high.
CON-15 AHR Low Freq
CON-16 AHR High Freq
Sets the lower limit frequency (CON-15) and the maxim limit
frequency (CON-16) for anti-hunting regulation.