Performing Basic Operations
64
890053-00-02
3.2.2 Switching Operation Modes (HAND / OFF / AUTO)
The H2 Series inverters have two operating modesthe HAND and AUTO modes. HAND mode is used
for local control using the keypad. AUTO mode is used for remote operation using the terminal inputs or
network commands.
3.2.2.1 HAND Mode Operation
Follow the instructions listed below to operate the inverter in HAND mode.
Press the [HAND] button. The inverter starts operating in HAND mode. The display is now in
the Monitor mode. The HAND LED turns on.
At the Monitor menu (Line 1 of the MON display) set the running frequency using the [Up],
[Down], [Left], and [Right] buttons.
Press the [OFF] button. The OFF LED turns on and the inverter stops operating.
3.2.2.2 AUTO Mode Operation
Follow the instructions listed below to operate the inverter in AUTO mode.
Press the [AUTO] button to switch to AUTO mode. AUTO LED is blinking.
Operate the inverter based on the settings of DRV-06, Cmd Source and DRV-07, Freq Ref
Src. The MON display will show these in the upper left corner (EX: T/V).
Press the [OFF] button. The OFF LED turns on and the inverter stops operating.
In AUTO mode, if DRV-06. Cmd Source is set as ‘keypad’, the Auto button will start
the inverter. If DRV-07, Freq Ref Src is set to Keypad (-1 or -2), the inverter will go
to the speed set in DRV-01, Cmd Frequency.
Pressing the HAND button starts the inverter.