Troubleshooting
344
890053-00-02
71 ~ PRT-77.
Broken Belt
Latch
Triggered when PRT-91 is set to Free Run. Related settings
in PRT-92 ~ PRT-95
Option Protection
LCD Display
Type
Description
Lost Command
Level
Displayed when a frequency or operation command error is
detected during inverter operation by controllers other than
the keypad (e.g., using a terminal block and a
communication mode). Activate by setting PRT-12 to any
value other than 0’.
IO Board Trip
Latch
Displayed when the I/O board or external communication
card is not connected to the inverter or has a bad
connection.
ParaWrite Trip
Latch
Displayed when communication fails during parameter
writing. Occurs due to a control cable fault or a bad
connection.
Option Trip-1
Latch
Displayed when a communication error is detected between
the inverter and the communication board. Occurs when a
communication option card is installed.
11.1.2 Warning Messages
LCD Display
Description
Over Load
Displayed when PRT-17 is set to 1 (Yes)’ to enable OL warning and
motor is overloaded. Related parameters PRT-17 ~ PRT-19. Set output
relays or Q1 (OUT-3135 or OUT-36) to ‘5 (Over Load)to receive the
overload warning output signals.
Under Load
Displayed when PRT-25 is to1 (Yes)’ and the motor is underloaded.
Related parameters PRT-25 ~ PRT- Set output relays or Q1 (OUT-31
35 or OUT-36) to7 (Under Load) to receive the underload warning
output signals.
INV Over Load
Displayed when the overload time equivalent to 60% of the inverter
overheat protection (inverter IOLT) level is accumulated. Set output
relays or Q1 (OUT-3135 or OUT-36) to6 (IOL)’ to receive the inverter
overload warning output signal.
Lost Command
Lost command warning alarm occurs even with PRT-12 set to0’. The
warning alarm occurs based on the condition set at PRT-13-15. Set
output relays or Q1 (OUT-3135 or OUT-36) to ‘13 (Lost Command)’ to
receive the lost command warning output signals.
Fan Warning
Displayed when an error is detected from the cooling fan while PRT-79 is
set to’1 (Yes). Set output relays or Q1 (OUT-3135 or OUT-36) to ‘8
(Fan Warning)’ to receive the fan warning output signals.
DB Warn %ED
Displayed when the DB resistor usage rate exceeds the set value. Set
the detection level at PRT-66.