5.7.3 OUT-41 Digital Output Status
Display the status of each output terminal. In parameter view, when the bottom segment is black, bit is
"OFF" (status is open). When the top segment is black, bit is "ON" (status is closed).
LCD bit representation in parameter view. When the bottom segment is black, bit is set to "OFF",
status is open. When top segment is black, bit is set to “ON”, status is closed.
Multi-function output
monitor
0 0000 0000
~
1 1111 1111
5.7.4 OUT-30 Fault Output using Relay or Q1 Terminals
With Relay1 ~ Relay5 or Q1 set to 23 (Trip), OUT-30 (Fault Output Mode) can further define relay
activation during low voltage faults, all faults and auto restart functions. Additionally, On and Off
delay times can also be applied to the outputs when set to 23 (Trip).
Multi-function relay2
setting
Multi-function relay3
setting
Multi-function relay4
setting
Multi-function relay5
setting
• FDT-1 and FDT-2 functions are related to the frequency setting of the inverter. If the inverter
enters standby mode by pressing the off button during auto mode operation, FDT-1 and
FDT-2 function operation may be different because the set frequency of the inverter is
different compared to the set frequency of the auto mode.
If monitoring signals such as ‘Under load’ or’ LDT’ are configured at multi-function output
terminals, signal outputs are maintained unless certain conditions defined for signal cutoff
are met.