5.7.5 OUT-50 Multi-function Output Terminal Delay Time Settings
Set On/Off delay times to adjust the relay operation time. The delay times set in OUT-50 and
OUT-51 will be applied to all Relays (1~5) and Q1 except when any are set to ‘23 (Trip)’.
Additionally, a NO or NC setting can be individually applied to the outputs.
Multi-function
output On delay
Multi-function
output Off delay
Select multi-
function output
terminal
0 0000 0000
~
1 1111 1111
Output Terminal Delay Time and NO/NC Setting Details
When the output is operated based on OUT-31~36 settings, it will activate
after the delay time set in OUT-50.
When the output is initialized based on OUT-31~36 settings, it will
deactivate after the delay time set in OUT-51.
Select relay output contact types (NO or NC) for each output relay. Type A
designates a normally open (NO) relay output. Type B designates a
normally closed (NC) relay output. LCD bit representation in parameter
view. When the bottom segment is black, bit is set to "OFF" (normally
open relay).
Output Terminal Delay Times