Parameter Lists
97
890053-00-02
4.2.8 Protection Group (PRT)
Code
Name
LCD
Display
Setting Range
Initial Value
Property*
Ref.
00
Jump Code
Jump Code
199
40
O
p.74
01
Back Spin Timer
Backspin Time
0.0 - 6000.0 (sec)
0
O
p.191
04
Load Duty
Load Duty
0
Normal Duty
0
Normal Duty
Δ
p.197
1
Heavy Duty
05
Input/output open-phase
protection
Phase Loss Chk
Bit
0011
00
Δ
p.192
Bit
0
Output open
phase
Bit
1
Input open
phase
06
Input voltage range during
open-phase
IPO V Band
1100 (V)
15
240V, 480V
O
p.192
40
575V
07
Deceleration time at fault
Trip Dec Time
0.0600.0 (sec)
3.0
240V: 7.5~60HP
O
p.195
480V: 7.5~125HP
575V
90.0
240V: 75~125HP
480V:150~800HP
08
Selection of startup on trip
reset
RST Restart
Bit
0011
00
O
p.192
Bit
0
Faults other
than LV trip
Bit
1
LV Trip
09
Number of automatic restarts
Retry Number
010
0
O
p.192
10
Automatic restart delay time
Retry Delay
0.1600.0 (sec)
5.0
O
p.192
11
Keypad command loss
operation mode
Lost KPD Mode
0
None
0
None
O
p.195
1
Warning
2
Free-Run
3
Dec
12
Speed command loss
operation mode
Lost Cmd Mode
0
None
0
None
O
p.195
1
Free-Run
2
Dec
3
Hold Input
4
Hold Output
5
Lost Preset
13
1
Time to determine speed
command loss
Lost Cmd Time
0.1120.0 (sec)
1.0
O
p.195
14
Operation frequency at speed
command loss
Lost Preset F
0.00, Low FreqHigh
Freq
0.00
O
p.195
15
Analog input loss decision level
AI Lost Level
0
Half of x1
0
Half of x1
O
p.195
1
Below x1
17
Overload warning selection
OL Warn Select
0
No
0
No
O
p.197
1
Yes
18
Overload warning level
OL Warn Level
30OL Trip Level(%)
110
O
p.197
19
Overload warning time
OL Warn Time
0.030.0 (sec)
10.0
O
p.197
20
Motion at overload trip
OL Trip Select
0
None
1
Free-Run
O
p.197
1
Free-Run
2
Dec
21
Overload trip level
OL Trip Level
30150 (%)
120
O
p.197
22
Overload trip time
OL Trip Time
0.060.0 (sec)
60.0
O
p.197
23
Under load detection Source
UL Source
0
Output Current
0
Output Current
Δ
p.199
1
Output Power
24
Under load detection band
UL Band
0.0100.0 (%)
10.0
Δ
p.199
25
Under load warning selection
UL Warn Sel
0
No
0
No
O
p.199
1
Yes
26
Under load warning time
UL Warn Time
0.0600.0 (sec)
10.0
O
p.199
27
Under load trip selection
UL Trip Sel
0
None
0
None
O
p.199
1
Free-Run
2
Dec
28
Under load trip timer
UL Trip Time
0.0600.0 (sec)
30.0
O
p.199
31
Operation on no motor trip
No Motor Trip
0
None
1
Free-Run
O
p.200
1
Free-Run
32
No motor trip current level
No Motor Level
1100 (%)
5
O
p.200
33
No motor detection time
No Motor Time
0.110.0 (sec)
3.0
O
p.200
34
Operation at motor overheat
detection
Thermal-T Sel
0
None
0
None
O
p.201
1
Free-Run
2
Dec

Table of Contents