Technical Specifications
357
890053-00-02
13 Technical Specifications
13.1 Input and Output Specifications
240 V, 7.5 HP - 25 HP (5.518.5 kW)
Model VFD-RSI-XXXH2-2C
007
010
015
020
025
240V
3φ Input
Normal Duty
120% OL
HP
7.5
10
15
20
25
kW
5.5
7.5
11
15
18.5
Amps
22
30
42
56
69
Heavy Duty
150% OL
HP
5
7.5
10
15
20
kW
3.7
5.5
7.5
11
15
Amps
17
24
32
46
60
240V
1φ Input
Normal Duty
120% OL
HP
3.0
5.0
7.5
10.0
-
Amps
11
16
23
30
37
Rated
Output
Rated Capacity (kVA)
8.4
11.4
16.0
21.3
26.3
Output Frequency
0400 Hz (V/Hz, Slip Comp.)
0-120 Hz (IM Sensorless)
0-180 Hz (PM Sensorless)
Output Voltage (V)
3-Phase 0240 V
Rated
Input
Voltage (V)
Three-Phase
3-Phase 200240 VAC (-15%+10%)
Single-Phase
1-Phase 240 VAC (-5%+10%)
Input
Frequency
Three- Phase
5060 Hz (+/-5%)
Single- Phase
60 Hz (+/-5%) only
Rated Current (A)
23.7
32.7
46.4
62.3
77.2
Weight lbs.
(kg)
7.3
(3.3)
7.3
(3.3)
7.3
(3.3)
10.1
(4.6)
15.6
(7.1)
Heat Dissipation (W)
180
248
330
451
600
Degree of Protection
IP20, UL Open (UL Type 1 achieved with optional conduit box)
• The horse power rating is based on a standard 4-pole motor rating.
• The KVA rating is based on a 220 V supply voltage for 240 V inverters.
• The rated output current is limited based on the carrier frequency set at CON-04.