Parameter Descriptions
153
890053-00-02
5.4.12 ADV-74 Press Regeneration Prevention
Press regeneration prevention is used during press operations to prevent braking during the
regeneration process. When motor regeneration occurs during a press operation, motor operation
speed automatically increases to avoid the regeneration zone.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
ADV
74
Select press
regeneration
prevention for press
RegenAvd Sel
0
No
0–1
-
75
Press regeneration
prevention operation
voltage level
RegenAvd
Level
350V
230V: 300-400V
V
700V
460V: 600-800V
870V
575V: 800-980V
76
Press regeneration
prevention
compensation
frequency limit
CompFreq
Limit
1.00(Hz)
0.00– 10.00Hz
Hz
77
Press regeneration
prevention P gain
RegenAvd
Pgain
50.0(%)
0 .0– 100.0%
%
78
Press regeneration
prevention I gain
RegenAvd
Igain
500(ms)
20–30000ms
ms
Press Regeneration Prevention Setting Details
Code
Description
ADV-74
RegenAvd Sel
Frequent regeneration voltage from a press load during constant speed motor operation may
force excessive work on the brake unit which may damage or shorten the brake life. To
prevent this situation, select ADV-74 (RegenAvd Sel) to control DC bus voltage and disable
the brake unit operation.
ADV-75
RegenAvd
Level
Set the DC bus voltage level to activate Regen Avoidance.
ADV-76
CompFreq
Limit
Set a frequency limit above operating frequency during Regen Avoidance.
ADV-77
RegenAvd
Pgain
ADV-78
RegenAvd
Igain
Set the P gain and I gain in the DC bus voltage suppressor PI controller while in Regen
Avoidance.
Note
Press regeneration prevention only operates during constant speed motor operation. It does
not operate during accelerations or decelerations. When regeneration prevention is activated,
output frequency may change within the range set at ADV-76 (CompFreq Limit).