5.4.12 ADV-74 Press Regeneration Prevention
Press regeneration prevention is used during press operations to prevent braking during the
regeneration process. When motor regeneration occurs during a press operation, motor operation
speed automatically increases to avoid the regeneration zone.
Select press
regeneration
prevention for press
Press regeneration
prevention operation
voltage level
Press regeneration
prevention
compensation
frequency limit
Press regeneration
prevention P gain
Press regeneration
prevention I gain
Press Regeneration Prevention Setting Details
Frequent regeneration voltage from a press load during constant speed motor operation may
force excessive work on the brake unit which may damage or shorten the brake life. To
prevent this situation, select ADV-74 (RegenAvd Sel) to control DC bus voltage and disable
the brake unit operation.
Set the DC bus voltage level to activate Regen Avoidance.
Set a frequency limit above operating frequency during Regen Avoidance.
ADV-77
RegenAvd
Pgain
ADV-78
RegenAvd
Igain
Set the P gain and I gain in the DC bus voltage suppressor PI controller while in Regen
Avoidance.
Press regeneration prevention only operates during constant speed motor operation. It does
not operate during accelerations or decelerations. When regeneration prevention is activated,
output frequency may change within the range set at ADV-76 (CompFreq Limit).