8.1.7 AP2-46 Lubrication Operation
Lubrication operation can be used for oil pump starters. The inverter outputs the lubrication signal
through one of the output relays when the inverter receives a run command. The inverter does not
start operating until the time set at AP2-46 (Lub Op Time) has elapsed and the Lubrication signal is
turned off.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP2
46
Lubrication
operation time
Lub Op Time
0.1600.0
(sec)
OUT
31-35
Multi-function relay
15
Relay 1–5
30 (Lubrication)
0-43
-
Lubrication Operation Setting Details
Code
Description
AP2-46
Lub Op Time
Outputs the lubrication signal for a set time when the inverter run command is
turned on. The inverter starts operating when the set time has elapsed.
OUT-3135
Relay 1–5
Sets one of the output relays (OUT-3135) to ‘30 (Lubrication) to enable
the Lubrication function.
Note
The lubrication function can be used to delay inverter operations, depending on the
working environment, since the inverter waits for the time set at AP2-46 (Lub Op Time)
each time a run command is received.
Lubrication operation is one of the essential system features that are available in both
HAND and AUTO modes.