5.6.4 Digital Input Descriptions
5.6.4.1 Fx, Rx (Forward, Reverse) Command Input
Px terminal setting
options
Assign a terminal for forward ‘1 (Fx)’ operation. Assign a terminal for reverse ‘2 (Rx)’ operation. Refer
to 5.1.3.2 Terminal Block as a Command Source (Fwd/Rev Run) on page 105 for additional details.
5.6.4.2 RST, Reset command input
After a fault, the inverter can be reset with a digital input set to ‘3, (RST)’ and activate the terminal
to reset the trip. A fault can also be reset by pressing the OFF button on the LCD.
Px terminal setting
options
5.6.4.3 External Trip
Set one of the multi-function (digital) input terminals P1~P7 (IN-65 ~ IN-71) to ‘4 (External Trip)’.
When activated, the inverter trips and blocks the output. The input terminals can be set
independently as NO or NC with IN-87 to activate the trip when closed or when opened.
Px terminal setting
options
Multi-function input
contact selection
0 0000 0000
~
1 1111 1111
External Trip Signal Setting Details
Select terminal input contact types (NO or NC) for each input terminal.
Type A designates a normally open (NO) contact input, close to
activate. Type B designates a normally closed (NC) contact input, open
to activate.
LCD bit representation in parameter view. When the bottom segment is
black, bit is set to "OFF" (normally open).