Parameter Descriptions
161
890053-00-02
5.6 Input Group (IN)
5.6.1 Analog Inputs
Refer to 5.1.4 DRV-07 Frequency Reference Source on page 107 for parameters related to the
analog inputs.
Terminal
Range
Parameters
Section
V1
0-10V
IN-05~IN-11
5.1.4.3
V1'
0- (-10)V
IN-12~IN-15
5.1.4.3.2
I2
4-20mA
IN-50~IN-56
5.1.4.4
I2(V2)
0-10V
IN-35~IN-40
5.1.4.4.2
TI
Pulsed 32kHz
IN-91~IN-98
5.1.4.5
S+,S-
RS-485
COM-01~COM-04
5.1.4.6
5.6.2 IN-60 Safe Operation Mode
This safety feature is used as a Run Enable/Disable input. When a digital input is set to 15 (Run
Enable), the inverter will only operate when the input is closed (Enabled). The input must be
closed to recognize other digital input functions. This feature is useful for interlocking operation
with other equipment.
A stop mode can be selected (IN-61, Run Dis Stop) when the Run Enable input is opened during
operation. Selections include coasting to stop, Quick Stop and Quick Stop Resume. The
deceleration time (IN-62, Q-Stop Time) can be set for the Quick Stop functions.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
IN
60
Safe operation
selection
Run En Mode
1
DI Dependent
-
-
61
Safe operation stop
mode
Run Dis Stop
0
Free-Run
0-2
-
1
Q-Stop
2
Q-Stop Resume
62
Safe operation
deceleration time
Q-Stop Time
5.0
0.0-600.0
sec
IN
65~71
Px terminal
configuration
Px Define
(Px: P1~P7)
15
RUN Enable
0-42
-