5.6.2 IN-60 Safe Operation Mode
This safety feature is used as a Run Enable/Disable input. When a digital input is set to 15 (Run
Enable), the inverter will only operate when the input is closed (Enabled). The input must be
closed to recognize other digital input functions. This feature is useful for interlocking operation
with other equipment.
A stop mode can be selected (IN-61, Run Dis Stop) when the Run Enable input is opened during
operation. Selections include coasting to stop, Quick Stop and Quick Stop Resume. The
deceleration time (IN-62, Q-Stop Time) can be set for the Quick Stop functions.