Safe Operation Mode Setting Details
Set one of the multi-function (digital) input terminals to 15 (RUN Enable)
to operate in safe operation mode.
Enables safe operation mode. Input must be
closed (Enabled) to operate.
Operation is in combination with the status of
Run command (Fx input).
Decelerates the motor based on the deceleration time (Q-Stop Time) set
in IN-62. If the Enable input is re-applied during deceleration and the run
command is maintained, the inverter will resume normal operation.
Blocks the inverter output when the multi-function
terminal is off.
The deceleration time (Q-Stop Time) used in safe
operation mode. It stops after deceleration and
then the operation can resume only when the
operation command is entered again. The
operation will not begin if only the multi-function
terminal is on.
The inverter decelerates to the deceleration time
(Q-Stop Time) in safe operation mode. It stops
after deceleration. Then if the multifunction
terminal is on, the operation resumes as soon as
the operation command is entered again.
Sets the deceleration time when IN-61 (Run Dis Stop) is set to 1 (Q-
Stop) or 2 (Q-Stop Resume).
Q-Stop Function
When IN-60 (Run En Mode) is set to 1 (DI Dependent) and IN-61 is set to 1 (Q-Stop), if the Run
Enable input is opened during operation, the inverter will decelerate to a stop based on the time
set in IN-62, Q-Stop Time. To re-start, the Enable input must be re-applied and the Run command
(Fx) must be removed then re-applied.
Q-Stop Resume Function
When IN-60 (Run En Mode) is set to 1 (DI Dependent) and IN-61 is set to 2 (Q-Stop Resume), this
allows operation (Start/Stop) of the inverter based on the Run Enable input. If the Run Enable is
opened during operation and the Run command (Fx) is maintained, closure of the Run Enable input
will allow the inverter to operate (resume operation).