Performing Basic Operations
78
890053-00-02
3.3.2 Monitoring Multiple Faults
The following example shows how to monitor multiple faults that occur at the same time.
3.3.3 Viewing Fault History
The fault history information can be viewed in the trip (TRP) mode. The inverter stores five (5) of the
most recent faults.
TRP Current
Over Voltage (02)
01 Output Frequency
36.00 Hz
02 Output Current
77.3 A
TRP Current
Over Voltage (02)
01 Over Voltage
02 External Trip
When more than one fault occurs at the same
time, the number of faults is displayed to the
right of the present fault.
Press the PROG/ENT button to display all
faults.
Press the down arrow button to view all faults.
Press the PROG/ENT button to display
information about the highlighted fault.
TRP Last-1
00 Trip Name (1)
Over Voltage
01 Output Frequency
36.00 Hz
02 Output Current
77.3 A
TRP Last-2
00 Trip Name (2)
External Trip
01 Output Frequency
57.00 Hz
02 Output Current
96.7 A
Press the right arrow button to move to the
next fault (Last-2) in the fault history.
•Press the MODE button to move to the trip
(TRP) mode. The most recent fault (Last-1) is
displayed.
Use the down arrow button to view this fault
information.