EasyManua.ls Logo

BENSHAW RSi H2 Series - Sensorless Vector Control Operation Guide

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sensorless Vector Control
244
890053-00-02
Note
Speed controller gain can improve the speed control waveform while monitoring the changes
in speed. If speed deviation does not decrease quickly, increase the speed controller P gain or
decrease I gain (time in ms). However, if the P gain is increased too high or I gain is decreased
too low, severe vibration may occur. If oscillation occurs in the speed waveform, try to increase
I gain (ms) or reduce P gain to adjust the waveform
7.1.2 Sensorless Vector Control Operation Guide
Problem
Function code
Troubleshooting
The amount of starting
torque is insufficient.
MOT-15 Tr
CON-09 PreExTime
CON-48 ACR SL P
Gain
CON-54–57 Trq Lmt
CON-93 SL Volt
Comp3
For large motors, increase CON-09. Set the value of CON-
09 to be more than 3 times the value of MOT-15.
Reduce the value of CON-48 by decrements of 10.
Increase the value of Trg Lmt (CON-54~57) by increments
of 10%.
Increase the value of CON-93 by increments of 5.
The output frequency is
higher than the base
frequency during no-load
operation at low speed
(10Hz or lower).
CON-91 SL Volt
Comp1
Decrease the value of CON-91 by decrements of 5.
The motor hunts (irregular
vibration) or the amount of
torque is not sufficient
while the load is increasing
at low speed (10Hz or
lower).
CON-04 Carrier
Freq
CON-24 ASR-SL P
Gain1
CON-25 ASR-SL I
Gain1
CON-91 SL Volt
Comp1
If the motor hunts at low speed, lower CON-24 or increase
CON-25 by increments of 50m/s. If hunting does not
occur, increase the value of CON-24 to find the optimal
operating condition.
If the amount of torque is insufficient, increase the value of
CON-91 by increments of 5.
In the 5-10Hz range, decrease the value of CON-04 by
increments of 1kHz (if CON-04 is set to exceed 3kHz).
Note that vibration may result if the set P-gain value is too
high or the set I-gain value is too low. If oscillation is
observed in the waveform, first increase the I-gain, and
then increase the P-gain to find the optimal values.
The motor hunts or
overcurrent trip occurs in
regenerative load at low
speed (10 Hz or lower).
CON-92 SL Volt
Comp2
CON-93 SL Volt
Comp3
Increase the value of CON-92 and CON-93 in increments
of 5.
Over voltage trip occurs
due to sudden
acceleration/deceleration
or sudden load fluctuation
(with no brake resistor
installed) at mid speed
(30Hz or higher).
CON-27 ASR-SL I
Gain2
Decrease the value of CON-27 by decrements of 5%.
Over current trip occurs
due to sudden load
fluctuation at high speed
(50 Hz or higher).
CON-54–57 Trq Lmt
CON-94 SL FW Freq
Decrease the values of CON-54-57 by decrements of 10%
(if the parameter setting is 150% or higher).
Increase/decrease the value of CON-94 by
increments/decrements of 5% (set below 100%).
The motor hunts when the
load increases from the
base frequency or higher.
CON-25 ASR-SL I
Gain1
CON-26 ASR-SL I
Gain2
Increase the value of CON-25 by increments of 50m/s or
decrease the value of CON-26 by decrements of 5%.
The motor hunts as the
load increases.
CON-31 S-Est P
Gain1
At low speed (10Hz or lower), increase the value of CON-
32 by increments of 5.

Table of Contents

Related product manuals