Sensorless Vector Control
CON-32 S-Est I
Gain1
CON-33 S-Est I
Gain2
At mid speed (30 Hz or higher), increase the value of
CON-31 by increments of 500. If the parameter setting is
too extreme, over current trip may occur at low speed,
lower CON-31 and increase CON-32.
The motor speed level
decreases.
Select 4, Tr (static type) from MOT-11 and run Rotor time
constant tuning.
If over current trip occurs
at starting.
Lower both the CON-48 and CON-49.
The motor cannot reach
the speed reference when
it is operated at or above
the rated speed, or when
the acceleration is not
responsive.
Increase the value at CON-50 in 1% increments if the
motor cannot reach the speed reference.
Increase the value at CON-51 in 10% increments if the
motor acceleration is not responsive.
Speed variation occurs at
rated motor speed, or
when excessive current
flows due to insufficient
voltage during high speed
operation.
If the motor is operated at the rated speed, decrease the
value at CON-50 in 5% increments.
If the motor response is slow, increase the value at CON-
51 in 5% increments.
Increase P Gains, Decrease I Gains.
If speed loss or OC trip
occurs.
CON-88 Flux I
Gain1
(below CON-95)
If current imbalance occurs
CON-89 Flux I
Gain2
(CON-95 below 9Hz)
Increase I Gains. If OLT occurs due to high I gains, lower I
gains.
If Speed error is negative
(-), compensate by
increasing Slip Comp.
CON-97 SL Slip
Comp1
CON-98 SL Slip
Comp2
For 575V inverter only. Comp1 is for motoring mode,
Comp2 is for generating mode. Increase to reduce speed
error.
*Hunting: Symptom of irregular vibration of the equipment.