5.8.17 PRT-81 Low Voltage Fault
When the internal DC bus voltage drops due to a power loss, the inverter turns off the output and
a low voltage fault occurs after the delay time set in PRT-81 (Low voltage fault delay time). When
the voltage recovers, the fault clears, and the inverter is ready to resume operation. Relay 1~5
(OUT-31~35) or Q1 (OUT-36) can be set to 11 (Low Voltage) to provide an output signal.
Low voltage trip
decision delay time
Low Voltage Fault Setting Details
If the parameter value is set to ‘11 (Low Voltage)’, the inverter stops the output
first when a low voltage trip condition occurs, then a fault occurs after the low
voltage trip decision time elapses. The warning signal for a low voltage fault can
be provided using the outputs. However, the low voltage trip delay time (LVT Delay
time) does not apply to warning signals.
5.8.18 PRT-82 Selecting Low Voltage 2 Fault During Operation
Low voltage trip
decision during
operation
Setting PRT-82 to ‘1 (Yes)’ which makes a low voltage condition a latched fault requiring a manual
reset. If the internal DC voltage decreases lower than a certain voltage, the inverter disconnects the
output and displays low voltage ‘2 (Low Voltage 2)'. Even if the voltage increases and goes back to
the normal state, unlike a low voltage fault, it remains in a fault state until manually reset.
5.8.19 PRT-90 Low Battery Voltage Warning
The H2 series has a battery used for the Real Time Clock (RTC). If the low battery voltage
warning function is set to ‘Yes,’ a low battery voltage warning occurs when the battery voltage is
lower than 2 V (normal voltage is 3 V). Replace the battery when the low battery warning is
displayed.
Low battery
voltage detection