Parameter Descriptions
101
890053-00-02
5 Parameter Descriptions
5.1 Drive Group (DRV)
5.1.1 DRV-01 Command Frequency
The following parameters are related to HAND-OFF-AUTO button operation. Refer to section 3.2.1 for
details.
Codes / Functions
Description
DRV-01
Cmd Frequency
Frequency reference in AUTO mode when DRV-07 is set to’ KeyPad’.
DRV-02
KeyPad Run Dir
Rotation direction of the keypad start/run command in the HAND or AUTO
mode.
DRV-05
KPD H.O.A Lock
To make HAND-OFF-AUTO buttons enabled/disabled.
DRV-25
HAND Cmd Freq
Frequency displayed at the monitor display item (Monitor Line-1) when the
HAND button is pressed in other modes (default frequency reference for
HAND mode).
DRV-26
HAND Ref Mode
Settings
Description
0
Hand
Parameter
The inverter operates based on the rotation direction
set at DRV-02 (Keypad Run Dir) and the frequency
reference set at DRV-25 (HAND Cmd Freq).
1
Follow Auto
The inverter takes over the rotation direction and the
frequency reference from the settings for AUTO
mode and keeps performing the same operation. If
the inverter was stopped in AUTO mode, the
operation direction is set as Fx and the frequency
reference is set as 0 (no inverter output).
OUT-3136
Relay 15, Q1
Set AUTO State (36) to ensure that the inverter is in AUTO mode.
OUT-3136
Relay 15, Q1
Set HAND State (37) to ensure that the inverter is in HAND mode.
Settings
0
Forward
1
Reverse
Settings
Description
0
Locked
HAND-OFF-AUTO buttons are disabled. If pressed,
Message displayed as:
KPD H.O.A Lock
1
During Run
If DRV-06, Cmd Source is Fx/Rx-1, Fx/Rx-2, Int485 or
fieldbus, HAND-OFF-AUTO buttons are disabled during
running.
3
Unlocked
HAND-OFF-AUTO buttons are enabled all the time.