5.8.5 PRT-17 Overload Trip and Early Warning
The inverter provides motor overload protection and will trip on an Overload Fault based on
amount of current (% motor amps) and time. The inverter responds to an overload fault based on
the setting of parameter PRT-20 (OL Trip Select). Select ‘1 (Free-Run)’ or ‘2 (Dec)’ to activate the
overload function and to determine the stop method when an overload fault occurs. Relay1~
Relay5 (OUT-31~35) or Q1 (OUT-36) can be set to ‘5 (Overload)’ to provide an output signal.
The inverter can also provide an overload warning (OLW) based on the settings of parameters
PRT-17 (OL Warn Select), PRT-18 (OL Warn Level) and PRT-19 (OL Warn Time). Set parameter
PRT-17 to ‘1 (Yes)’ to activate the overload warning function. Set the output current level in
parameter PRT-18, set the time in PRT-19. Relay1~ Relay5 (OUT-31~35) or Q1 (OUT-36) can be
set to ‘5 (Overload)’ to provide an output warning signal. The inverter does not trip when
warning levels are reached.
A fault or warning occurs when the motor reaches an overload state based on the motor’s rated
current and the PRT settings. The amount of current for trips and warnings can be set separately.