10 seconds before the loss of the speed reference and
uses it as the speed reference.
The inverter calculates the average output value for
10 seconds before the loss of the speed reference and
uses it as the speed reference.
The inverter operates at the frequency set at PRT- 14
(Lost Preset F).
PRT-15
AI Lost Level
PRT-13
Lst Cmd Time
Configure the voltage level and time delay for speed reference loss
detection when using analog input.
Based on the minimum analog input values set at IN-
08 (V1), IN-12 (V1’), IN-38 (V2) and IN-53 (I2),
protection operates when the input signal is reduced to
half of the initial value of the analog input and after the
time (PRT-13) has expired.
Example: Set the speed reference to ‘5 (I2)’ at DRV-07,
and set IN-53 (I2 min.) to 4 mA. When the 4mA input
drops to less than half (2mA), the protective function is
activated after the set time (PRT-13).
The protective function operates when the analog input
signal falls below the minimum values set at IN-08
(V1), IN-12 (V1’), IN-38 (V2) and IN-53 (I2) and after
the time (PRT-13) has expired.
NOTE: If the minimum value of the analog input is ‘0’, the LostCmd function
does not operate.
To run at a fixed speed, set the operation mode (PRT-12 Lost Cmd Mode) to
‘5 (Lost Preset)’. When the protection function operates, this sets the
frequency for continued operation.
EX: Speed Ref Loss below 5V. Set IN-06 (V1 Polarity) to ‘Unipolar’ and IN-08 to ‘5 (V)’. Set PRT-
15 (AI Lost Level) to ‘1 (Below x1)’ and PRT-12 (Lost Cmd Mode) to ‘2 (Dec)’ and then set PRT-13
(Lost Cmd Time) to 5 seconds. Then the inverter operates as follows:
Note
When using communications or RS-485 for speed reference, if speed reference is lost the
protection operates based on the time set at PRT-13 (Lost Cmd Time).