Sensorless Vector Control
Sensorless voltage
compensation 2
20 (230V, 460V)
110 (575V)
Sensorless voltage
compensation 3
Sensorless field
weakening start
frequency
Sensorless gain
switching frequency
Sensorless Slip
Compensation1
Sensorless Slip
Compensation2
7.1.1 Sensorless Vector Control Operation Setting
To run sensorless vector control operation, set DRV-09 (Control Mode) to 3 (IM sensorless), select the
capacity of the motor at MOT-01 (Motor Capacity), and enter the nameplate information of the motor
in the below parameters.
Input (Motor Name Plate Information)
Efficiency (when no information is on the name plate, default values are used.)
After setting the above, set MOT-11 (Auto tuning) to 1 (All - rotation type) or 2 (All - static type) and
run auto tuning. Rotation type auto tuning is more accurate than Static type. Set 1 (All -Rotation type)
if the motor can be rotated.
Excitation Current
A motor can be operated only after magnetic flux is generated by current flowing through the
stator. When the motor is connected to the output of the inverter, excitation current flowing in
the stator creates the magnetic flux required to operate the motor.
Sensorless Vector Control Operation Setting Details
Sets the excitation current application time. Pre-excitation is used at
the start of the operation to perform excitation up to the motor’s rated
flux.
Sets the zero-speed control time (hold time) after deceleration in the
stopped position. The inverter applies an output (at zero speed) to hold
the motor for the Hold Time, CON-11. The output is blocked after the
Hold Time.