5.6.23 Time Event En
A digital input can be set to ’35 (Time Event En)’. When activated, the scheduling set in the Event Timer of
Application Group 3 (AP3) is performed. Refer to 8.2 Application Group 3 (AP3) on page 269 for details
on the Event Timer.
Px terminal setting
options
5.6.24 Pre Heat
A digital input can be set to ’36 (Pre Heat)’. When activated, current is applied to the motor to remove
moisture and prevent freezing. Refer to 8.1.8 AP2-48 Pre-Heat Function on page 267 for details on setting
the current level and time.
Px terminal setting
options
5.6.25 Damper Open
A digital input may be set to ‘45 (Damper Open)’ to receive the damper open status input. Refer to
section 8.1 AP2-45 Damper Operation on page 265 for more details.
Px terminal setting
options
5.6.26 Pump Clean
A digital input can be set to ’38 (Pump Clean)’ to perform the Pump Cleaning Operation. Refer to
section 8.1.3 AP2-15 Pump Clean Operation on page 259 for more details.
Px terminal setting
options
5.6.27 Sleep Wake Chg
A digital input can be set to ’39 (Sleep Wake Chg)’ to switch between two different Sleep/Wake Up
settings, Sleep/Wake Up 1 (AP1-07~AP1-10) and Sleep/Wake Up 2 (AP1-11 ~ AP1-14). Refer to
section 6.3.2 PID Sleep Mode on page 233 for more details.
Px terminal setting
options