8.1.5 AP2-40 Start & End Ramp Operation
This function is used to rapidly accelerate the pump to the normal operating level, or to rapidly
decelerate the pump and stop it. Start & End ramp operation is performed when ADV-24 (Freq
Limit) is set to ‘1 (Yes).’
Start & End Ramp
Gradient
Start & End Ramp Operation Setting Details
Sets the pump Start & End Ramp options.
The Start & End Ramp operation is not used.
Use the Start & End Ramp operation.
Refers to the time it takes to reach the minimum pump operation frequency
for a Start & End Ramp operation (Freq Limit Lo) set at ADV- 25 when the
inverter starts (it is different from DRV-03 acceleration slope).
Refers to the time it takes to reach the 0 step (stop) from the minimum pump
operation frequency for a Start & End Ramp operation (Freq Limit Lo) set at
ADV-25 (it is different from DRV-03 deceleration slope).
In the figure above, AP2-41 defines the acceleration time to the minimum operation frequency
ADV-25 (Freq Limt Lo). AP2-42 defines the deceleration time from the minimum operation
frequency to a stopped state. Time A (normal acceleration time set at DRV-03) and Time B (normal
deceleration time set at DRV-04) in the figure will change according to the Acc/Dec slopes defined
by AP2-41 and AP2-42.