Parameter Descriptions
163
890053-00-02
5.6.3 Digital Inputs
The digital input terminals (P1 ~ P7) can be set to a variety of functions. The following table
shows the default settings of parameters IN-65 ~ IN-71.
Code
Name
LCD Display
Setting
IN-65
P1 terminal configuration
P1 Define
1
Fx
IN-66
P2 terminal configuration
P2 Define
2
Rx
IN-67
P3 terminal configuration
P3 Define
5
BX
IN-68
P4 terminal configuration
P4 Define
3
RST
IN-69
P5 terminal configuration
P5 Define
7
Speed-L
IN-70
P6 terminal configuration
P6 Define
8
Speed-M
IN-71
P7 terminal configuration
P7 Define
9
Speed-H
IN-72*
P8 terminal configuration
P8 Define
0
None
IN-73*
P9 terminal configuration
P9 Define
0
None
* IN-72 and IN-73 are shown when the Extended IO Card is installed.
The following table lists the various functions that can be assigned to the digital input
terminals.
Setting
Description
Setting
Description
0
None
Not assigned
22
U/D Clear
Clear the saved U/D speed
1
Fx
Forward Start/Run
23
Analog Hold
Hold the analog input speed reference
2
Rx
Reverse Start/Run
24
I-Term Clear
Clear the accumulated I-Gains
3
RST
Reset
25
PID Openloop
Switch to V/Hz mode.
4
External Trip
External Trip
26
PID Gain2
Switch to PID Gain2 setting
5
BX
Disable Output
27
PID Ref Change
Switch PID reference
6
JOG
Jog Operation
28
Pre Excite
Apply DC to motor at start
7
Speed-L
Fixed Speed - Low
29
Timer In
Activate timer for relay output
8
Speed-M
Fixed Speed - Medium
31
dis Aux Ref
Disable the Auxiliary speed reference
9
Speed-H
Fixed Speed - High
32
FWD JOG
Start at forward jog speed
11
XCEL-L
Multi-Step Accel/Decel - Low
33
REV JOG
Start at reverse jog speed
12
XCEL-M
Multi-Step Accel/Decel - Medium
34
Fire Mode
Activate Fire Mode
13
XCEL-H
Multi-Step Accel/Decel - High
35
Time Event En
Activate Time Event schedule
14
XCEL Stop
Disable XCEL Steps
36
Pre Heat
Apply DC to motor while stopped
15
RUN Enable
Run enable/disable
37
Damper Open
Detect Open Damper state
16
3-Wire
3 wire control
38
Pump Clean
Perform Pump Clean operation
17
2nd Source
Switch to 2nd control and frequency
reference sources
39
Sleep Wake Chg
Use 2nd Sleep/Wake settings
18
Exchange
Switch inverter output to line
40
PID Step Ref L
Step reference (Low) for PI Control
19
Up
Increase speed
41
PID Step Ref M
Step reference (Medium) for PI Control
20
Down
Decrease Speed
42
PID Step Ref H
Step reference (High) for PI Control