Parameter Descriptions
105
890053-00-02
5.1.3.2 Terminal Block as a Command Source (Fwd/Rev Run)
Digital input terminals can be selected as the start/stop command source. Set DRV-06 (command
source) to 1 (Fx/Rx-1). The default settings for terminals P1 and P2 are 1 (Fx) and 2 (Rx) respectively.
Or set any (2) of the corresponding parameters (IN-65~IN-71) to 1 (Fx) and 2 (Rx). Activating either
terminal constitutes a run command. Activating both terminals constitute a stop command.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
DRV
06
Command source
Cmd Source
1
Fx/Rx-1
05
-
IN
6571
Px terminal
configuration
Px Define
(Px: P1 P7)
1
Fx
042
-
2
Rx
Fwd/Rev Command by Multi-function Terminal Setting Details
Code
Description
DRV-06
Cmd Source
Set to 1 (Fx/Rx-1).
IN-6571
Px Define
Assign a terminal for forward (Fx) operation. Assign a terminal for reverse
(Rx) operation.
5.1.3.3 Terminal Block as a Command Source (Run and Direction)
Set parameter DRV-06 (command source) to 2 (Fx/Rx-2). This configuration (Fx/Rx-2) assigns the Fx
terminal as the Start/Stop input terminal and assigns the Rx terminal as the rotational direction input
terminal (Open: Fwd, Closed: Rev). Set (2) of the corresponding parameters (IN-65~IN-71) to 1 (Fx)
and 2 (Rx) respectively.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
06
Command source
Cmd Source
2
Fx/Rx-2
05
-
IN
6571
Px terminal
configuration
Px Define
(Px: P1 P7)
1
Fx
042
-
2
Rx

Table of Contents