5.7 Output Group (OUT)
5.7.1 OUT-01, OUT-07 Analog Outputs
Each of the analog output terminals (AO1, AO2) can represent one of a variety of functions. AO1
is switchable (SW5 on IO TB PCB) between 0/4-20mA or 0-10V outputs. AO2 is 0-10V output
only. Scaling and filtering can also be applied to the output signals. A 0-32kHz pulsed output can
be provided at terminal Q1 (OUT-36 set to ’38 (TO)’.
5.7.1.1 Voltage and Current Analog Output
Voltage and Current Analog Output Setting Details
OUT-01
AO1 Mode
OUT-07
AO2 Mode
Select the function of the signal to output.
Outputs operation frequency as a standard. 10V
output is made from the frequency set at DRV-20
(Max Freq)
A 10V output represents 150% of inverter rated
current.
Sets the outputs based on the inverter output
voltage. 10V output is made from a set voltage in
MOT-07 (Motor Voltage).
If ‘0’ is set in MOT-07, 230V/460V inverter’s output
10V based on the actual input voltages.
Outputs inverter DC bus voltage as a standard.
Outputs 10V when the DC bus voltage is 410Vdc
for 230V inverters, and 820Vdc for 460V models.
Monitors output wattage. A 10V output represents
150% of inverter rated power.
Outputs set frequency as a standard. Outputs 10V
at the maximum frequency (DRV-20).