Multi-function Input Terminal Control Setting Details
IN-83
DI On Delay En
IN-84
DI Off Delay En
Each input terminal (P1~P9) can be set to function with an On Delay
and/or an Off Delay. Apply an “On Delay” function for selected
terminals with IN-83. Apply an “Off Delay” function for selected
terminals with IN-84.
LCD bit representation in parameter view. When the top segment is
black, bit is set to "ON".
IN-85
DI On Delay
IN-86
DI Off Delay
Set the On/Off delay times for all of the enabled terminals in IN-83
and IN-84. When the terminal receives a change of state input it is
recognized as On or Off after the set time.
Select terminal input contact types (NO or NC) for each input
terminal. Type A designates a normally open (NO) contact input,
close to activate. Type B designates a normally closed (NC) contact
input, open to activate.
LCD bit representation in parameter view. When the bottom segment
is black, bit is set to "OFF" (normally open).
Display the status of each input terminal. In parameter view, when
the bottom segment is black, bit is "OFF" (status is open). When the
top segment is black, bit is "ON" (status is closed).