EasyManua.ls Logo

BENSHAW RSi H2 Series - H2 Expansion Common Area Parameter

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
315
890053-00-02
10.3.8 H2 Expansion Common Area Parameter
10.3.8.1 Monitoring Area Parameter (Read Only)
Comm.
Address
Parameter
Scale
Unit
Assigned content by bit
0h0300
Inverter model
-
-
H2: 000Fh
0h0301
Inverter capacity
-
-
0.75 kW: 4008h, 1.5 kW: 4015h
2.2 kW: 4022h, 3.7 kW: 4037h
5.5 kW: 4055h, 7.5 kW: 4075h
11 kW: 40B0h, 15 kW: 40F0h
18.5 kW: 4125h, 22 kW: 4160h
30 kW: 41E0h, 37 kW: 4250h,
45 kW: 42D0h,55 kW: 4370h,
75 kW: 44B0h,90 kW: 45A0h,
110 kW: 46E0h, 132 kW: 4840h
160 kW: 4A00h, 185kW: 4B90h,
220 kW: 4DC0h, 250 kW: 4FA0h,
315 kW: 53B0h, 355 kW: 5630h,
400 kW: 5900h, 500 kW: 5F40h
0h0302
Inverter input
voltage/power
(Single phase, 3-
phase), cooling
method
-
-
200 V 3-phase forced cooling: 0231h
400 V 3-phase forced cooling: 0431h
600 V 3-phase forced cooling: 0831h
0h0303
Inverter S/W version
-
-
(ex) 0h0064: Version 1.00
0h0065: Version 1.01
0h0304
Reserved
-
-
-
0h0305
Inverter Operation
State
-
-
B15
0:Normal State
4:Warning occurred
8:Fault occurred
B14
B13
B12
B11
-
B8
B7
1: Speed searching
2: Accelerating
B6
3: Operating at constant
rate
4: Decelerating
B5
5: Decelerating to stop
6: H/W OCS
B4
7: S/W OCS
8: Dwell operating
B3
0: Stopped
1: Operating in forward
direction
B2

Table of Contents