EasyManua.ls Logo

BENSHAW RSi H2 Series - Page 328

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
316
890053-00-02
Comm.
Address
Parameter
Scale
Unit
Assigned content by bit
B1
2: Operating in reverse
direction
3: DC operating
B0
0h0306
Inverter operation
frequency command
source
-
-
B15
Operation command
source 0: Keypad
1: Communication option
3: Built-in RS 485
4: Terminal block
B14
B13
B12
B11
B10
B9
B8
B7
Frequency command
source 0: Keypad speed
1: Keypad torque
2-4: Up/Down operation
speed
5: V1, 7: V2, 8: I2
9: Pulse
0: Built-in RS 485
11: Communication option
13: Jog
14: PID
25-31: Multi-step speed
frequency
B6
B5
B4
B3
B2
B1
B0
0h0307
Keypad S/W version
-
-
(Ex.) 0h0064: Version 1.00
0h0308
Keypad title version
-
-
(Ex.) 0h0065: Version 1.01
0h0309
IO Board Version
-
-
(Ex.) 0h0064: Version 1.00 (Ex.)
0h0065: Version 1.01
0h030A
0h30F
Reserved
-
-
-
0h0310
Output current
0.1
A
-
0h0311
Output frequency
0.01
Hz
-
0h0312
Output rpm
0
Rpm
-
0h0313
Reserved
-
-
-
0h0314
Output voltage
1
V
-
0h0315
DC Link voltage
1
V
-
0h0316
Output power
0.1
kW
-
0h0317
Reserved
-
-
-
0h0318
PID reference
0.1
%
PID reference value
0h0319
PID feedback
0.1
%
PID feedback value
0h031A
Display the number
of poles for the 1st
motor
-
-
Displays the number of poles for the
first motor

Table of Contents

Related product manuals